LIVEAI PMDC Digital Twin

40 FT / STUDIO 3D

40 ft AI Prefabricated Modular Data Center

Interactive engineering simulation | D2C Liquid Cooling | N+1 | Double Control

!
Review requiredEngineering checks not all passed
40 FT / STUDIO 3DContainer, racks & liquid loops
800 kW IT
SETEK 40 ft AI PMDC studio illustration showing eight GPU racks, overhead orange coolant return piping, blue coolant supply line, CDU and outdoor dry cooler
GPU Racks8 × 100 kW
CDU (N+1)3 × 500 kW
Dry Cooler1,000 kW
MODEL 40 · STUDIO VISUAL
Liquid-cooled AI infrastructure800 kW IT · 720 kW D2C
PHYSICAL: REVIEW · THERMAL: PASS
Drag to rotate · scroll to zoom
SETEK ENGINEERING VIEW
ϟ IT load800 kW
♧ Liquid heat load720 kW
≋ Residual air heat80 kW
〰 Water flow · estimated860 L/min
▤ Facility input · estimated873 kW
♧ Illustrative PUE1.09
♨Thermal Map — Rack Heat Distribution
36 °C20 °C
Illustrative thermal distribution, not measured temperatures
⟳Cooling Loop (D2C) — Calculated
Supply to racks24.0 °C
›››
Return from racks36.0 °C
ΔT12 °C
Calculated water flow: 860 L/min
↗Power & PUE — Scenario Trend
1.20.90.60.306h12h18h24h
Facility power 873 kWPUE 1.09
Constant-load illustration; not historical measurements.
LIVE CALCULATED PERFORMANCECalculated from inputs · not sensor telemetryContainer, racks & liquid loops
Coolant supplyCoolant return

Photorealistic illustrative image, not OEM CAD.

Reference calculation only. Net dimensions 11.90 × 2.35 × 2.55 m, 600 × 1,000 × 2,000 mm rack, 900 mm front aisle, 250 mm rear buffer, 350 mm overhead pipe allowance and water properties are assumptions. PUE uses illustrative UPS efficiency (97%), pump (1.2% of liquid heat), air COP (3.0) and heat-rejection fans (1.8% of liquid heat). Real design requires enclosure fabrication drawings, OEM capacity/pressure curves, hydraulic design, fault analysis, electrical single-line, fire safety and FAT/SAT approval.

Discuss a project ↗AI PMDCSETEK Home